text.skipToContenttext.skipToNavigation

General Electric Heater Coil

Heater Selection Information

To prevent overloading the starter, do not select heater(s)
for a motor of larger rating than the maximum given on the
nameplate for the starter.

For continuous rated motors, with a service factor of 1.15 to
1.25,select the heater with maximum motor amperes equal
to or immediately greater than the motor full-load current
(provides a maximum of 125 percent protection). For
continuous rated motors with no service factor, multiply the
full-load current of the motor by 0.90 and use this value to
select the heater.

How to Select Heaters

The table below should be used to determine which column of
motor full load amperes applies for heater selection. Select in
order, the base catalog number, the NEMA type of enclosure,
and the column to be used in the proper table by NEMA size.
If full-load amperes of the motor falls between two ratings,
select heaters for the higher rating.

Series Description Heater Table Column
CR306 3 phase, 3 pole, 3 leg protection standard C
ambient compensated (except size 3 & 4) D
ambient compensated size 3 D
ambient compensated size 4 E

Table for CR110H & CR110Y Manual Starters … click here

General Electric
NEMA SIZES 00, 0 and 1 NEMA SIZE 2 NEMA SIZE 3
Catalog
Number
Maximum Motor – Full Load Amps Catalog
Number
Maximum Motor – Full Load Amps Catalog
Number
Maximum Motor – Full Load Amps
A B C D A B C D C D
CR123C118A 1.12 1.09 1.04 1.02 CR123C592A 5.92 5.79 CR123F357B 31.8 31.3
CR123C131A 1.26 1.22 1.15 1.10 CR123C630A 6.23 6.12 5.85 5.72 CR123F430B 37.6 34.3
CR123C695A 6.63 6.49 6.47 6.30 CR123F487B 41.9 40.9
CR123C148A 1.40 1.31 1.27 1.23 CR123C778A 7.72 7.59 7.35 7.04
CR123C163A 1.46 1.46 1.39 1.38 CR123C867A 8.96 8.71 8.06 7.91 CR123F614B 52.1 51.1
CR123C184A 1.63 1.59 1.55 1.49 CR123F772B 68.1 63.3
CR123C196A 1.79 1.74 1.73 1.67 CR123C104B 10.4 10.1 9.61 9.27
CR123C220A 1.97 1.93 1.89 1.79 CR123C113B 11.7 11.2 10.5 9.99 CR123F848B 71.5 66.1
CR123C125B 12.1 11.9 11.6 11.1 CR123F114C 90.0 90.0
CR123C239A 2.25 2.13 2.05 1.98 CR123C137B 13.5 12.6 12.5 12.1
CR123C268A 2.43 2.37 2.28 2.24 CR123C151B 14.7 14.5 13.6 13.1
CR123C301A 2.60 2.52 2.47 2.43
CR123C326A 2.96 2.87 2.79 2.75 CR123C163B 18.3 17.7 16.7 15.5
CR123C356A 3.57 3.39 3.31 3.25 CR123C180B 20.1 19.1 17.9 16.8
CR123C198B 22.3 21.4 18.7 18.0
CR123C379A 3.86 3.59 3.70 3.43 CR123C214B 25.0 22.9 20.4 19.7
CR123C419A 4.43 4.31 4.06 4.03 CR123C228B 27.7 24.7 22.7 21.6
CR123C466A 4.87 4.57 4.47 4.43
CR123C526A 5.37 5.31 4.95 4.94 CR123C250B 29.3 25.9 24.7 23.9
CR123C592A 5.99 5.86 5.49 5.36 CR123C237B 30.7 27.1 26.3 25.5
CR123C303B 32.7 30.2 29.5 28.2
CR123C630A 6.39 6.19 5.91 5.77 CR123C330B 35.6 34.8 32.5 31.6
CR123C695A 6.87 6.61 6.47 6.35
CR123C778A 7.71 7.61 7.20 6.92 CR123C400B 45.0 45.0 41.9 37.8
CR123C867A 8.72 8.46 8.22 7.99 CR123C440B 43.2 40.6
CR123C104B 10.5 10.4 9.67 9.19
CR123C113B 11.7 11.3 10.4 10.0
CR123C125B 12.2 11.9 11.0 10.7
CR123C137B 13.5 13.0 12.4 12.0
CR123C151B 15.1 14.5 13.2 12.9
CR123C163B 17.5 17.4 15.4 15.1
CR123C180B 18.9 18.6 17.1 16.3
CR123C198B 20.8 20.5 18.1 17.9
CR123C214B 22.4 22.3 20.0 19.7
CR123C228B 25.5 25.7 22.5 21.2
CR123C250B 26.2 25.7 22.5 22.3
CR123C273B 27.0 27.0 23.9 22.3
CR123C303B 26.3 25.5
CR123C330B 27.0 27.0

The table below gives a proper size heater to trip the switch
at approximately 125 per cent of motor current.
Listed values are for motors with 1.15/1.25 service factor.
For continuous rated motors with a service factor of 1.0,
multiply full-load current of motor by 0.9 and use this value
to select heater. If motor full-load amperes falls between
two ratings, select heater for the higher rating.
For 1.35 service factor motors, multiply full-load current of
motor by 1.15 and use this value to select heater(s).

Max Full-load amps Heater Catalog Number
3.88 CR123H446A
4.60 CR123H529A
5.00 CR123H575A
5.43 CR123H625A
6.41 CR123H739A
6.98 CR123H802A
8.25 CR123H950A
10.6 CR123H122A
13.6 CR123H157A

Cutler-Hammer Heater Coil


Magnetic Motor Control

Heater coils are rated to protect 40½°C rise motors, and open and
drip-proof motors having a service factor of 1.15 where the motor
and the controller are at the same ambient temperature.

For other conditions:

  1. For 50½°C, 55½°C, 75½°C rise motors and enclosed motors having
    a service factor of 1.0, select one size smaller coil.
  2. Ambient temperature of controller lower than motor by 26½°C
    (47½°F) use one size smaller coil.
  3. Ambient temperature of controller higher than motor by 26½°C
    (47½°F) use one size larger coil.

Ultimate tripping current of heater coils is approximately 1.25
times the minimum current rating listed in the tables.

Manual Motor Control

Heater coils are rated to protect standard 40°C rise motors, and
open and drip proof motors having a service factor of 1.15 at
approximately 125% of rated motor current, and where controller and
motor are at same ambient.

Heater coil ranges provide for variations in all enclosure sizes
and designs, including internal heating. Selection tables are not
compromises or averaged values thereby providing maximum motor
output and life.

For other conditions:

  1. 50½°C or 55½°C rise motor and enclosed motor having a service
    factor of 1.0 with protection at 115% of rated current, use one
    size smaller coil.
  2. Ambient temperature of controller lower than motor by:
    8.5-16.7½°C (16-30½°F) use one size larger coil.
    16.8-27.8½°C(31-50½°F) use two sizes smaller coil.
  3. Ambient temperature of controller higher than motor by:
    8.5-16.7½°C (16-30½°F) use one size larger coil. 16.8-27.8½°C
    (31-50½°F) use two sizes larger coil.
Desc Type 00-1½ 2 3 4 5
A10 Open
Encl
ST-1
ST-2
ST-3
ST-4
ST-5
ST-6
ST-7
ST-8
ST-16
ST-16
A30 Encl ST-9 ST-3 ST-6 ST-8 ST-16
A40 Encl ST-9 ST-3 ST-6 ST-8 ST-16
A50 Open
Encl
ST-1
ST-2
ST-3
ST-4
ST-5
ST-6
ST-7
ST-8
ST-16
B10 both ST-1 ST-3 ST-5 ST-7
B50 both ST-1 ST-3 ST-5 ST-7
C300 both ST-1 ST-3 ST-5 ST-7
Desc NEMA Open 1
MS Series all See table
B100 Series all See table
Cutler-Hammer A10 Heater Selection Chart
For OPEN Type Cat. No. A10, A50, B10, B50, C300.

For ENCLOSED Type Cat. No. B10, B50, C300

For ENCLOSED Type Cat. No. A10, A50 For OPEN Type Cat. No. A10, A50, C300.

For ENCLOSED type Cat. No. B10, C300, A800

For ENCLOSED Type Cat. No. A10, A30, A50 For OPEN Type Cat. No. A10, A50, C300.

For ENCLOSED type Cat. No. B10

For ENCLOSED Type Cat. No. A10, A30, A50 For OPEN Type Cat. No. A10, A50, C300 For ENCLOSED Type Cat. No. A10, A50
Catalog Number Table ST-1 Table ST-2 Table ST-3 Table ST-4 Table ST-5 Table ST-6 Table ST-7 Table ST-8
Starter Size – Full Load Amps
Sizes 00, 0, 1, 1 ½ Size 2 Size 3 Size 4
H1101
H1102
H1103
H1104
H1105
.167-.187
.188-.210
.211-.237
.238-.266
.267-.298
.155-.173
.174-.195
.196-.220
.221-.247
.248-.278
























H1106
H1107
H1108
H1109
H1110
.299-.334
.335-.376
.377-.422
.423-.474
.475-.532
.279-.310
.311-.349
.350-.391
.392-.441
.442-.495
























H1111
H1112
H1113
H1114
H1115
.533-.598
.599-.672
.673-.757
.758-.855
.856-.959
.496-.555
.556-.624
.625-.703
.704-.795
.796-.895
























H1116
H1117
.960-1.07
1.08-1.21
.896-.999
1.00-1.12






H1018
H1019
H1020
H1021
H1022
1.22-1.35
1.36-1.52
1.53-1.70
1.71-1.90
1.91-2.10
1.13-1.25
1.26-1.41
1.42-1.58
1.59-1.77
1.78-1.96
























H1023
H1024
H1025
H1026
H1066
H1027
2.11-2.33
2.34-2.62
2.63-2.93
2.94-3.27
3.28-3.64
3.65-4.06
1.97-2.17
2.18-2.44
2.45-2.72
2.73-3.04
3.05-3.38
3.39-3.73





3.72-4.10

























H1028
H1029
H1030
H1031
H1032
4.07-4.55
4.56-5.03
5.04-5.59
5.60-6.25
6.26-6.92
3.74-4.18
4.19-4.63
4.64-5.15
5.16-5.68
5.69-6.30
4.11-4.59
4.60-5.07
5.08-5.65
5.66-6.29
6.30-7.00
3.86-4.31
4.32-4.77
4.78-5.31
5.32-5.90
5.91-6.55
















H1033
H1034
H1035
H1036
H1037
6.93-7.75
7.76-8.63
8.64-9.59
9.60-10.6
10.7-11.9
6.31-7.05
7.06-7.76
7.77-8.63
8.64-9.51
9.52-10.5
7.01-7.82
7.83-8.79
8.80-9.67
9.68-10.8
10.9-12.0
6.56-7.33
7.34-8.15
8.16-9.00
9.01-10.1
10.2-11.2

8.32-9.27
9.28-10.1
10.2-11.4
11.5-12.8

8.24-9.19
9.20-10.1
10.2-11.3
11.4-12.7








H1038
H1039
H1040
H1041
H1042
12.0-13.3
13.4-14.7
14.8-16.6
16.7-18.8
18.9-21.2
10.6-11.8
11.9-13.1
13.2-14.8
14.9-16.7
16.8-18.9
12.1-13.4
13.5-14.9
15.0-17.6
17.7-19.0
19.1-21.5
11.3-12.5
12.6-13.9
14.0-15.7
15.8-17.5
17.6-19.8
12.9-14.3
14.4-16.0
16.1-17.8
17.9-20.3
20.4-22.9
12.8-14.1
14.2-15.8
15.9-17.7
17.8-20.1
20.2-22.7




20.6-23.3




20.6-23.3
H1043
H1044
H1045
H1046
H1047
21.3-23.9
24.0-27.0


19.0-21.3
21.4-24.1
24.2-27.0

21.6-24.5
24.6-27.9
28.0-32.0
32.1-36.6
36.7-41.8
19.9-22.3
22.4-25.4
25.5-28.7
28.8-32.5
32.6-36.6
23.0-26.0
26.1-29.5
29.6-33.5
33.6-37.8
37.9-42.8
22.8-25.5
25.6-28.9
29.0-32.5
32.6-36.7
36.8-41.0
23.4-26.3
26.4-30.8
30.9-34.0
34.1-38.3
38.4-43.4
23.4-26.0
26.1-30.5
30.6-33.6
33.7-37.9
38.0-42.9
H1048
H1049
H1050
H1051
H1052








41.9-45.0



36.7-41.0
41.1-45.0


42.9-48.5
48.6-55.1
55.2-62.3
62.4-69.5
69.6-79.1
41.1-46.0
46.1-51.8
51.9-58.6
58.7-64.6
64.7-72.7
43.5-49.3
49.4-55.8
55.9-63.1
63.2-70.4
70.5-79.9
43.0-48.2
48.3-54.6
54.7-61.2
61.3-67.6
67.7-75.9
H1054
H1055
H1056
H1057
H1058
















79.2-90.0



72.8-83.1
93.2-90.0


80.0-91.7
91.8-105
106-121
122-135
76.0-87.1
87.2-97.5
97.6-109
110-122
123-135
Heaters for A200 or B100 Manual Starters
Motor Full-Load Current Catalog Number
1.40 – 1.54 FH19
1.55 – 1.71 FH20
1.72 – 1.89 FH21
1.90 – 2.10 FH22
2.11 – 2.32 FH23
2.33 – 2.54 FH24
2.55 – 2.79 FH25
2.80 – 3.07 FH26
3.08 – 3.36 FH27
3.37 – 3.68 FH28
3.69 – 4.03 FH29
4.04 – 4.40 FH30
4.41 – 4.81 FH31
4.82 – 5.26 FH32
5.27 – 5.74 FH33
5.75 – 6.26 FH34
6.27 – 6.83 FH35
6.84 – 7.45 FH36
7.46 – 8.11 FH37
8.12 – 8.81 FH38
8.82 – 9.58 FH39
9.59 – 10.40 FH40
10.41 – 11.30 FH41
11.40 – 12.20 FH42
12.30 – 13.50 FH43
13.60 – 14.90 FH44
15.00 – 16.00 FH45
16.10 – 17.10 FH46
17.20 – 18.30 FH47
18.40 – 19.70 FH48
19.80 – 21.20 FH49
21.30 – 22.80 FH50
22.90 – 24.50 FH51
24.60 – 26.40 FH52
26.50 – 28.50 FH53
28.60 – 30.80 FH54
30.90 – 33.30 FH55
33.40 – 36.00 FH56
36.10 – 38.90 FH57
11.90 – 13.00 FH68
13.10 – 14.30 FH69
16.00 – 17.40 FH71
17.50 – 19.10 FH72
19.20 – 21.10 FH73
21.20 – 23.20 FH74
23.30 – 25.60 FH75
25.70 – 28.10 FH76
28.20 – 30.80 FH77
30.90 – 34.50 FH78
34.60 – 38.20 FH79
38.30 – 42.60 FH80
42.70 – 46.00 FH81
47.00 – 51.00 FH82

Color Application for HID Lamps


Clear Mercury Landscape lighting, specialized floodlighting such as copper roofs
DX Mercury Stores, public spaces – Multi-vapor; however, are preferred
MV Stores, public spaces, industrial, gymnasiums, floodlighting signs
& buildings, parking areas, sports
MV/C Same as MV – warmer color – diffuse coating reduces brightness
LU Street lighting, parking areas, industrial, floodlighting,
security, CCTV
LU/DX Floodlighting, parking areas, indoor/outdoor pedestrian malls,
industrial security, roadway

Occupancy Sensor Application Guide

Sensor Type Catalog Number Appropriate Application
Small Offices
Automatic Wall Switch WS3000 Small, Individual Offices. Sensors should have a direct, clear
front view of stationary occupants. Be sure sensors will not be
blocked by doors, filing cabinets, etc.
360° Ceiling Mount or Wide Angle CS1001WA1001 Small, Individual Offices where wall switch location is a problem.
for offices with general activities, the wide area unit will work
well placed in the corner. If there are obstacles present, the CS
1001 will provide 360° coverage from the center of the office.
Ultrasonic US1001 Offices with large obstacles or stationary workers. The US1001
covers up to 750 sq. ft., detects around obstacles, and is more
sensitive to small movements than PIR (Passive Infrared) sensors.
It should be placed close to the area of activity and out of view
of doors so waves do not exit the room.
Conference and Training Rooms
360° Ceiling Mount CS1001 Small Conference rooms where a ceiling mount sensor is required.
They should be located where they will have a clear view of the
entire room but cannot see out the door.
Automatic Wall Switch WS3000 Small conference rooms under 300sq. ft. To ensure detection at the
far end of a room, it is recommended that the wall switch sensor be
within 20′ of the farthest wall.
Ultrasonic US1001 Small conference rooms without moving equipment that may falsely
activate the sensor. The US1001 works well in a room up to
750sq.ft. Multiple sensors may be used in larger rooms.
Wide Angle WA1001 Medium size conference rooms (400-1000sq.ft.) without obstacles
that may block a PIR sensor’s view.
360° Ceiling Mount or Wide Angle CS1001 WA1001 Conference rooms 1000 – 2500sq.ft. Two WA 1001 will work well when
installed in opposite corners. One of the sensors should be placed
to immediately sense occupants entering the room. For rooms greater
than 2500 sq ft. use multiple CS1001 or WA1001 sensors in zones.
Lunch, Copy and Utility Rooms
Automatic Wall Switch/Ultrasonic WS3000 US1001 An automatic wall switch sensor will work well in rooms smaller
than 300 sq ft; however, if occupants spend lengthy periods of time
behind cabinets or other structures, an ultrasonic sensor is a
better choice.
Restrooms
Ultrasonic US1001 Due to the many partitions in commercial restrooms, an ultrasonic
ceiling mount \sensor is needed. Multiple sensors may be used in
larger restrooms.
Hallways
PIR Wall Mount HS1001 In hallways without obstruction or where coverage masking is
required, HS1001 PIR sensors are perfect. When mounted between 10′
and 14′ high, they provide a coverage area of up to 10′ x 90′.
Sensors should be focused on areas where people will be entering
the space.

Occupancy Sensor Design Guide

DO

  • Use Ultrasonic sensors in areas screened by partitions or
    furniture
  • Use PIR in enclosed spaces
  • Create zones controlled by different sensors to manage lighting
    in large areas
  • Use dual technology sensors for areas with very low activity
    levels
  • Install sensors on a vibration-free, stable surface
  • Position sensors above or close to the main areas of activity
    in a space
  • Mask the sensor lens to define coverage of the controlled zone
    even more accurately
  • Integrate sensor use with other control methods (i.e. scheduled
    control, day lighting)
  • Educate occupants about the new devices and what to expect

DON’T

  • Use ultrasonic sensors in spaces with heavy air flow
  • Install ultrasonic sensors in spaces where the ceiling height
    exceeds 14 feet.
  • Use PIR sensors in spaces where there are fixtures or furniture
    that obstruct a clear line of sight
  • Install PIR sensors so that their line of sight continues
    beyond doorways
  • Install sensors within 6-8 feet of HVAC outlets or heating
    blowers
  • Position a wall switch sensor behind an office door
  • Control emergency or exit lighting with sensors
  • Install PIR sensors in spaces where there are extremely low
    levels of occupant motion

Basic Proximity Sensor Operations

Sensing:

The inductive proximity will sense all metals. The exact point
at which a target will be detected is influenced by the type of
metal, its size and surface area. The following charts show the
sensing fields for a standard target: 45mm sq., mild steel, 1mm
thick.

Standard Range

Shielded – Can be mounted flush with metal surface.

Extended Range

Non-shielded – Can not be mounted flush with metal surface

The two most common approach directions are axial (head-on) and
lateral (from the side). Detection occurs at the point where the
target first touches the envelope of the sensing curve. The curve
shown is for a standard target and must be corrected for other size
targets.

Correction Factors for Typical Target Materials Based on Standard Size

Target Material Corrective Factor
Steel 1020 1.00
430 Stainless 1.03
302 Stainless .85
Brass .50
Aluminum .47
Copper .40

Operation of Photo-Electric Sensors

Diffuse-Reflective

This type of sensor detects the reflection of transmitted light
from the surface of an object. Shortest sensing range of all
photoelectrics.

Retro-Reflective

This type of sensor utilizes a special reflector to return the
beam directed at it from the sensor. An object between the sensor
and reflector is senses when it interrupts the beam. Medium sensing
range.

Thru-Beam

Separate emitter and receiver provide maximum detection range
and most positive type of sensing for opaque objects. When an
object interrupts the beam from emitter to receiver, the object is
detected.


Operation of 2-wire and 3-wire sensors

A/C 2 Wire NO

2-Wire Devices: 2-wire sensors are intended to be connected tin
series with the controlled load. Because these sensors derive the
power to energize their internal electronics through the load they
control, a minimum current is drawn through the load when the
sensor is in the open stat. This current is so small that it can be
ignored and will not turn on electro-mechanical devices such as
relays and solenoids. However, this current could be enough to
operate an electronic load. Cutler-Hammer’s 2-wire sensors have the
lowest leakage current in the industry and are suitable for many
electronic loads.

A/C 3 wire NO/NC or DC PNP

3-WIRE DEVICES: 3-wire sensors derive their power directly
across the line and therefore have no current leakage to the
load.


Operation of Logic Modules
On Delay Adjustable delay between time object is sensed and time switch
function occurs.
Off Delay Adjustable delay between time object leaves sensing field &
time switch transfers back to non-sensing state.
On & Off Combination of Above.
Delayed Single Shot Adjusts length of time switch remains in “ON’ cycle after
object is sensed regardless of length of time object stays in
sensing field. “ON” cycle can also be delayed after object is first
detected.

Hazardous Location Basics


Definitions

HAZARDOUS LOCATION: An Area where the possibility of
explosion and fire is created by the presence of flammable gases,
vapors, dusts, fibers or flying.

Classes

CLASS I (NEC-500-4): Those areas in which flammable
gases or vapors may be present in the air in sufficient quantities
to be explosive or ignitable.

CLASS II (NEC-500-4): Those areas made hazardous by the
presence of combustible dust.

CLASS III (NEC-500-6): Those areas in which there are
easily ignitable fibers or flying present, due to type of material
being handled, stored, or processed.

Divisions

DIVISION 1 (NEC-500,4,5,6): Division One in the normal
situation, the hazard would be expected to be present in everyday
production operations or during frequent repair and maintenance
activity.

DIVISION 2 (NEC-500,4,5,6): Division Two in the abnormal
situation, material is expected to be confined within closed
containers or closed systems and will be present only through
accidental rupture, breakage, or unusual faulty operation.

Groups

GROUPS (NEC-500-2 & 502-1): The gases of vapors of
Class I locations are broken into four groups by the code.
A, B, C, and D. Theses materials are grouped according to the
ignition temperature of the substance, its explosion pressure and
other flammable characteristics.

CLASS II: dust locations – groups E, F, and G. These
groups are classified according to the ignition temperature and the
conductivity of the hazardous substance.

Seals

SEALS (NEC-501-5 & 502-5): Special fittings that are
required either to prevent the passage of hot gasses in the case of
an explosion in a Class I area of the passage of combustible dust,
fibers, or flyings in a Class II or III area.

ARTICLES 500 Through 503 (1978 NEC): Explain in detail
the requirements for the installation of wiring of electrical
equipment in hazardous locations. These articles along with other
applicable regulations, local governing inspection authorities,
insurance representatives, and qualified engineering/technical
assistance should be your guides to the installation of wiring or
electrical equipment in any hazardous or potentially hazardous
location.

Typical Class I Locations:

  • Petroleum refineries, and gasoline storage and dispensing
    areas.
  • Industrial firms that use flammable liquids in dip tanks for
    parts cleaning or other operations.
  • Petrochemical companies that manufacture chemicals from gas and
    oil.
  • Dry cleaning plants where vapors from cleaning fluids can be
    present.
  • Companies that have spraying areas where they coat products
    with paint or plastics.
  • Aircraft hangars and fuel servicing areas.
  • Utility gas plants, and operations involving storage and
    handling of liquefied petroleum gas or natural gas.

Typical Class II Locations:

  • Grain elevators, flour and feed mills.
  • Plants that manufacture, use, or store magnesium or aluminum
    powders.
  • Plants that have chemical or metallurgical processes or
    plastics, medicines and fireworks, etc.
  • Producers or starch or candies.
  • Spice-grinding plants, sugar plants and cocoa plants.
  • Coal preparation plants and other carbon-handling or processing
    areas.

Typical Class III Locations:

  • Textile mills, cotton gins, cotton seed mills, and flax
    processing plants.
  • Any plant that shapes, pulverizes, or cuts wood and creates
    sawdust or flyings.

NOTE: fibers and flyings are not likely to be suspended in
the air, but can collect around machinery or on lighting fixtures
and where heat, a spark, or hot metal can ignite them.:

Heat Dissipation in Electrical Enclosures

Selection Procedure:

  1. Determine input power in watts per square feet by dividing the
    heat dissipated in the enclosure (in watts) by the enclosure
    surface area (in square feet).
  2. Locate on the graph the appropriate input power on the
    horizontal axis and draw a line vertically until it intersects the
    temperature rise curve.
  3. Read horizontally to determine the enclosure temperature rise

Example:

What is the temperature rise that can be
expected from a 48″ x 36″ x 16″ enclosure with 300 watts of heat
dissipated within it?

Solution:

Surface Area = 2[(48×36) + (48×16) + (36×16)] divided by 144 =
42 square feet

Input Power = 300/42 = 7.1 Watts/SqFt.

From Curve: Temp. Rise = 30°F (16.7°C)

Blackouts

What are they?

Power failures, also known as blackouts, are the easiest power
problem to diagnose. If the lights go out, chance are there has
been a power failure. Any temporary, or not so temporary,
interruption in the flow of electricity will result in a power
failure which can cause hardware damage and data loss.

Where do they come from?

Violent weather is the first thing that comes to mind, but there
are any number of other causes. Overburdened power grids, car
accidents that bring down power lines, lightning strikes, and human
error are all likely sources.

What can they do?

Power failures are more than simply inconvenient and annoying.
They can cause computer users to lose hours of work when systems
shut down without warning. Power failures can even damage hard
drives resulting in loss of all data on a system. Consider the fact
that a single power outage on a high traffic network can stall
hundreds of users, and the seriousness of power failures becomes
evident. Even worse, when the power returns, it often brings
after-blackout spikes and surges to cause even more damage.

What can be done?

Computer users should consider a UPS system to protect their
systems. These systems monitor line levels and switch over to
battery power when utility power fails.

Brownouts

What are they?

Brownouts are periods of low voltage in utility lines that can cause lights
to dim and equipment to fail. Also known as voltage sags, this is the most
common power problem, accounting for up to 87% of all power disturbances.

Where do they come from ?

Overburdened utilities sometimes reduce their voltage output to deal with
high power. Recent statistics show that the US population tries to pull an
average of 5% more than the utility companies can provide. The demand for
power is rapidly increasing, but the supply of power is not. Damage to
electrical lines and other factors can also cause utility brownouts.
Locally, equipment that draws massive amounts of power such as motors, air
conditioners, etc. that can cause momentary brownouts to occur.
Undervoltages are often followed by overvoltages – “spikes” – which are
also damaging to computer components and data.

What do they do?

Voltage variation can be the most damaging power problem to threaten
equipment. All electronic devices expect to receive a steady voltage (120
VAC in North America) in order to operate correctly. Brownouts place undue
strain on power supplies and other internal components, forcing them to
work harder in order to function. Extended brownouts can destroy electrical
components and cause data glitches and hardware failure.

What can be done?

Surge suppressors do only 1/2 the job. Line conditioners and
Uninterruptible Power Supplies (UPS) are the best defense against both
voltage problems. Designed to regulate both over and under voltages, Line
Conditioners provide three separate levels of voltage correction. Adjusting
computer-grade AC power meeting ANSI C84.1 specifications.

Power Surges and Spikes


What are They?

Power surges are an increase in the voltage that powers
electrical equipment. Surges often go unnoticed, often
lasting only 1/20th of a second, but they are much more common and
destructive than you might think. According to recent
studies, electrical equipment is constantly experiencing surges of
varying power. Some of them can be absorbed by a power supply
while others can only be handled by a quality surge
suppressor. The most destructive power surges will wipe out
anything that gets in their way!

Where do they come from ?

In this power-hungry computer age, utility power systems are
often pushed beyond their capacity, resulting in unstable,
unreliable power for consumers. Overburdened power grids can
generate powerful surges as they switch between sources or generate
“rolling surges” when power is momentarily disrupted. Local
sources can also generate surges (such as a motor starting, or a
fuse blowing out).

What about Lightning?

Lightning can generate a spectacular surge along any conductive
line to destroy everything in its path. No matter what
manufacturers may claim, no surge suppressor in the world can
survive a direct lightning strike.
However, with quality
equipment the surge suppressor will take the hit – ending up melted
– but the equipment it protects will not be affected.

Choosing the Right Level of Protection

Joule Ratings: The bigger, the better! Joule
ratings measure a surge suppressors ability to absorb surges.

  • 200 Joules: Basic Protection
  • 400 Joules: Good Protection
  • 600+ Joules: Excellent Protection

Surge Amp Ratings: Higher ratings offer more
protection. Amp levels are another important factor in
determining surge strength. Look for the highest amp
protection levels available.

UL 1449 Voltage Let-Through Ratings: Underwriter
Laboratories tests each surge suppressor and rates them according
to the amount of voltage they let-through to connected
equipment. The lower the let-through voltage, the better the
surge suppressor is. UL established the 330 volt let-through
as the benchmark because lower ratings added no real benefits to
equipment protection, while surge components, forced to work
harder, failed prematurely. Be wary of manufacturers claiming
lower let-through ratings.

Line Noise

What is it?

The term "line noise" refers to random fluctuations-electrical
impulses that are carried along with standard AC current. Turning on
fluorescent lights, laser printers, working near a radio station, using a
power generator, or even working during a lightening storm can all
introduce line noise into systems.

What can it do?

Line noise interference can result in many different symptoms depending on
the situation. Noise can introduce glitches and errors into programs and
files. Hard Drive components can be damaged. Televisions and computer
screens can display interference as "static" or "snow,"
and audio systems experience increased distortion levels.

What can be done?

Surge suppressors, Line conditioners and UPS units include special noise
filters that remove or reduce line noise. The amount of filtration is
indicated in the technical specifications for each unit. Noise suppression
is stated as Decibel level (dB) at a specific frequency (kHz or MHz). The
higher the dB, the greater the protection.

Be wary of "surge/noise suppressors" that don’t provide this
information. Some surge suppressors (Such as the Tripp Lite Isobar
suppressors) take noise suppression to a new level with Isolated Filter
Banks. These special banks prevent line noise generated from one device
from traveling through the surge suppressor to interfere with other
equipment.

Using a laser printer (a notorious source for line noise) connected to the
same suppressor that powers a computer will not endanger the computer.

Lamp Guide: Incandescent

Incandescent Filament Designations

Filament
designations consist of a letter or letters to indicate how the
wire is coiled, and an arbitrary number sometimes followed by a
letter to indicate the arrangement of the filament on the supports.
Prefix letters include C (coil) — Wire is would into a helical
coil or may be deeply fluted; CC (coiled coil) — wire is would
into a helical coil and this coiled wire again wound into a helical
coil. some of the more commonly used types of filament arrangements
are illustrated.

C-2V
CC-2V
C-5 C-6
CC-6
CC-6 C-7A C-8
2CC-8 C-9 C-11
CC-11
C-13
CC-13
C-17A C-2R
CC-2R
MP BP FF M SC CC-6
CC-8

Incandescent Base Types

Incandescent Base Types

Incandescent Base Types

Incandescent Bulb Shapes

The size and shape of a bulb is designated by a letter or letters
followed by a number. The letter indicates the shape of the bulb
while the number indicates the diameter of the bulb in eighths of
an inch. For example “T-10” indicates a tubular shaped bulb having
a diameter of 10/8 or 1 1/4 inches. The following illustrations
show some of the more popular bulb shapes and sizes.

A B BA
Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes
A-19 A-21 A-23 B-10 1/2 B-13 BA-9 BA-9 1/2
BR C ER
Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes
BR-19 BR-25 BR-30 BR-40 C-7 ER-30
F G K P
Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes
F-10 F-15 F-20 G-16 1/2 G-25 G-40 K-19 P-25
PAR PS
Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes
PAR-16 PAR-20 PAR-30S PAR-30L PAR-36 PAR-38 PAR-64 PAR-64 PS-35
R RP S
Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes
R-20 R-30 R-40 R-40 RP-11 S-6 S-11 S-14
T
Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes Incandescent Bulb Shapes
T-4 1/2 T-5 T-6 T-8 T-8 T-10

Lamp Guide: HID

 

High Intensity Discharge Base Type (Not Actual Size)

 

High Intensity Discharge Bulb Shapes (Not Actual Size)

The size and shape of a bulb is designated by a letter or letters followed
by a number. The letter indicates the shape of the bulb while the
number indicates the diameter of the bulb in eighths of an inch.
For example “T-7” indicates a tubular shaped bulb
having a diameter of 2 1/8 inches. The following illustrations
show some of the more popular bulb shapes and sizes.

Lamp Guide: Fluorescent

Miniature
Bipin T-5
Min. Bipin
Medium
Bipin T-8/T-10/T-12
Med. Bipin
Recessed Double
Contract T-8/T-12
Recessed D.C.
Slimline
Single Pin
T-8/T-12
Circleline
4-Pin

The size and shape of a bulb is designated by a letter or
letters followed by a number. The letter indicates the shape of
the bulb while the number indicates the diameter of the bulb in
eighths of an inch. For example “T-10” indicates a tubular
shaped bulb having a diameter of 10/8 or 1 1/4 inches. The
following illustrations show some of the more popular bulb
shapes and sizes.

The size and shape of a bulb is designated by a letter or
letters followed by a number. The letter indicates the shape of
a bulb while the number indicates the diameter of the bulb in
eighths of an inch. For example, “T-12” indicates a tubular
bulb having a diameter of 12/8 or 1 1/2 inches. The following
illustrations show some more popular bulb shapes and sizes.

T-5 Miniature Bipin
T-8 Medium Bipin
T-10 Medium Bipin
T-12 Medium Bipin
T-8 Recessed Double Contact
T-12 Recessed Double Contact
T-12 Recessed Double Contact (Jacketed)
T-8 Single Pin Slimline
T-12 Single Pin Slimline
T-8 Medium Bipin U-Bent Lamp
T-12 Medium Bipin U-Bent Lamp (6″)
T-12 Medium Bipin U-Bent Lamp (3″)
T-9 4-Pin Circline
Earth Light Lamps
Earth Light Lamp Bulb Shapes SL/O Earth Light Lamp Bulb Shapes SL/T Earth Light Lamp Bulb Shapes SL/R40 Earth Light Lamp Bulb Shapes SLS/G40
SL/O SL/T SL/R40 SLS/G40
Earth Light Lamp Bulb Shapes SL/O Earth Light Lamp Bulb Shapes SL/T Earth Light Lamp Bulb Shapes SL/R40
SLS 9,11 SLS 15,20,23,25 SLS/R30, R40
PL Lamps
PL Adapter System (First 2)
Earth Light Lamp Bulb Shapes SL/O Earth Light Lamp Bulb Shapes SL/T Earth Light Lamp Bulb Shapes SL/R40
PL-S/SYS PL-C/SYS PL-S
PL Replacement Bulb (All 3)
Earth Light Lamp Bulb Shapes SL/O Earth Light Lamp Bulb Shapes SL/T Earth Light Lamp Bulb Shapes SL/R40
PL-C PL-L PL-T

Lamp Guide: General Information

Maximum Overall Length (in inches)- includes the sockets for
incandescent bulbs and pins for fluorescent bulbs (MOL).

Lamp Diameter – Lamp diameter is expressed in eighths of
an inch (1/8″). For example: an A21 bulb is 21 – eighths of an
inch or 2 5/8″ in diameter at it’s maximum dimension
(DIA).

Beam Spread Legend-

(NSP – NARROW SPOT) (SP – SPOT) (NFL – NARROW
FLOOD) (FL – FLOOD)

Incandescent HID Compact Fluorescent Fluorescent
DIAMOL DIA
MOL
MOL Nominal Length is the dimension from back of socket to back of
socket