OSIRIS™XM Expansion Module Posted on November 14, 2016November 15, 2016 by Brandy McNeil Double or triple the point count of an OSIRIS unit. OSIRIS™XM Expansion Module OSI Remote Information System Expansion Module hardware © Copyright 2006-2014, Open Systems International, Inc. All rights reserved. Ver. 3.0 All other trademarks and registered trademarks are the property of their respective holders. www.osii.com OSIRIS XM Product Overview XM DC Power Fuse Expansion Connector Digital Outputs Digital Inputs Analog Inputs Power Switch Module Select Switch Local/Remote Switch OSIRIS™XM (OSI Remote Information System Expansion Module) is a convenient and affordable way to add I/O expansion to OSI’s OSIRIS™ Linux-based secure Remote Terminal Unit (RTU). OSIRIS XM can double or triple the point count of an OSIRIS unit (up to 48 Digital Inputs, 24 Relay Outputs and 24 DC Analog Inputs), effectively transferring the versatility, security and power of OSIRIS to additional points. OSIRIS XM is identical to OSIRIS in point count, terminal blocks can be transferred without disturbing field wiring, and it is seamlessly supported by the OSIRIS configuration utility. It utilizes the built-in security features of OSIRIS to deliver secure communications over serial or IP-based connections. OSIRIS XM General Specifications Power Requirements + 20V – 60V DC + Optional External Universal Power Supply Environmental Monitoring + Communications & Health LED Operating Conditions + Operating Temperature -40° to 80°C (-40° to 176°F) + Utility Grade: meets IEEE C37.90.1, IEC 61000-4-4 Analog Inputs + (8) optically isolated 16-bit analog inputs + ±1V, ±5V, ±10V, ±1mA or 4-20mA inputs or as specified Digital Inputs + (16) optically isolated digital inputs + 12, 24, 48, or 125V bi-polar wetting voltage + Optional internal wetting voltage + 1ms time stamp resolution with configurable COS (Change of State) and SOE (Sequence of Events) recording Digital Outputs + (8) clean contact Form C relay outputs + Pulse on or hold + Select Before Operate (SBO) functionality + Maximum constant current: 6A + Maximum momentary current (5 sec): 10A + Maximum switched current: 10A @ 240VAC, 8A @ 30VDC + Maximum switched voltage: 240V AC/DC Mounting + Compact Size: 10 x 8.69 x 1.63 inches (25.5 x 22 x 4.2 cm) + DIN rail + Panel + 1U 19” Rack + Custom enclosures available Expansion Bus + Robust 2-wire multi-drop communication Product specifications in this document are subject to change without notice.