PRODUCT NOTICE
Notice of Potential Product Concern
Rockwell Automation issues a Product Notice when it identifies a product(s) anomaly that may cause commercial or customer satisfaction concerns.
AADvance Workbench 1.x and 2.x Performing Restore from Repository
Reference: 2020-07-003
Date: July 2020
This Product Notice informs you of a potential anomaly that exists with the AADvance® Workbench 1.x and 2.x. If a controller application is modified by an online update following a controller restore, the communications between that controller and other controllers may stop. When a SNCP producing controller is replaced by importing an exchange file or by a project restore, it is required that you compile / build the entire project and update all controllers.
– Product Identification –
The affected products are:
• AADvance Workbench 1.x – Catalog numbers T9082U, T9082D, T9083U, T9083D, and T9084U
• AADvance Workbench 2.x – Catalog number T9087
PRODUCT NOTICE
Page 2 of 6
expanding human possibility™
– Description –
A potential anomaly exists with the AADvance Workbench 1.x and 2.x. If a controller application is modified by an online update following a controller restore, the communications between that controller and other controllers may stop. When a SNCP producing controller is replaced by importing an exchange file or by a project restore, it is required that you compile / build the entire project and update all controllers.
The SNCP bindings between controllers may cease when a single controller, or not all controllers are updated in a distributed project restored from the repository. All the following conditions must be met for the anomaly to occur:
• The project has been restored in the repository (*.vsc) or modified by importing an exchange file (*.pxf)
• An online update is performed, and
• Not all of the controllers are updated.
This anomaly does not impact the binding “Consume Status Variable” or the “Error Variables” behavior. Using the second parameter, communication loss can be detected in the logic by configuring the “Use default Value”. An example is provided below with:
• Consume Status Variable: ConsumerLinkVariable, shown in Figure 2 below.
• Error Behavior: Use Value of: : -999, shown in Figure 2 & 3 below.
Also, the Consume status variable will display an error code different than 0 when the communication loss occurs. This variable is configured in Figure 1 below.
Figure 1: Consume Status Variable – AADvance 2.x
PRODUCT NOTICE
Page 3 of 6
expanding human possibility™
Figure 2: Error behavior configuration – AADvance 2.x
Figure 3: Communication error identification – AADvance 2.x
PRODUCT NOTICE
Page 4 of 6
expanding human possibility™
– Temporary Workarounds –
This anomaly may be corrected by performing a full build and download of all controllers following restore of a project from the repository or modified by importing an exchange file.
– Correction –
Correction of this anomaly requires updating to SISW 2.0 or later. Rockwell Automation is currently working on this release and will update the Knowledgebase article associated with this notification when SISW 2.0 is available for download and installation. As of the release of this notification, SISW 2.0 is anticipated to be released in early 2022.
Until correction can be implemented, users are advised to implement the actions in the Temporary Workarounds section of this notification.
– Requested Customer Action –
Rockwell Automation requests you take the following actions:
• Check if you have a product affected by this Product Notice. Refer to the Product Identification and Description sections of this document for product identification assistance.
• Customers under support contract are automatically eligible for software updates. Customers not under a support contract should contact Rockwell Automation for further instructions.
• If you need additional assistance, please contact Rockwell Automation Technical Support. See Appendix A for local telephone numbers. Customers without TechConnect℠ support contracts should reference this Product Notice when calling.
• Customers with TechConnect support contracts may be able to chat online with support representatives. Reference this Product Notice when connected to a support engineer.
The most current version of this Product Notice is posted on the Rockwell Automation Support Center, http://www.rockwellautomation.com/knowledgebase, as ID number PN1514 / 1127005. Additional languages may also be available at the end of this article attached as downloadable PDF documents.
If this Product Notice does not affect you because you do not have the products any longer, or if you are a Distributor, Rockwell Automation asks that you forward a copy of this notice, with any identifying documentation, immediately to the person or company that now has the product. We also ask that you contact Rockwell Automation Technical Support and provide the location of the affected units.
We appreciate your immediate cooperation. If you have any questions, please contact us.
Sincerely,
ROCKWELL AUTOMATION
PRODUCT NOTICE
Page 5 of 6
expanding human possibility™
You can register for Automatic Product Safety Advisories and Product Notices from Rockwell Automation by email. Go to the Support web page at http://www.rockwellautomation.com/support and click the Search Knowledgebase – Get Answers link. Sign in with your TechConnect Account or free Rockwell Automation Member Account and you can subscribe to important product updates, including Product Safety Advisories and Product Notices.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
PRODUCT NOTICE
Page 6 of 6
expanding human possibility™
Appendix A
Regional Technical Support Information
The following list can help you to contact the correct technical support center for your location. If your country is not listed, you can find a customer support number for your location by going to the Rockwell Automation Knowledgebase as https://rockwellautomation.custhelp.com. Click on Contact Us → Phone, and then enter your location information. If you have a TechConnect℠ support contract, please use the telephone number supplied to you with the contract.
Region / Country
Phone Number ( ) International Code
Region / Country
Phone Number ( ) International Code
Asia/Pacific
Europe
Australia
1 800 762 593
Austria
(49) 211 41553 664
China
400 620 6620
Belgium
(32) 2 716 8411
Hong Kong
+852 2887 4666
Czech Republic
(420) 28401 5911
India
1 800 2000 121
Denmark
(45) 43 466 006
Japan
03 3206 2785
Finland
(358) 958 447 419
Korea
(82) 2 2188 4400
France
(33) 825303132
Malaysia
1 800 80 4851
Germany
(49) 211 41553 664
New Zealand
0800 27 27 25
Hungary
(420) 28401 5911
Taiwan
080 902 0908
Ireland
(44) 01908 635245
Thailand
(66) 2936 1500
Italy (Brescia, Milano e Padova)
(39) 199 11 99 00
Caribbean
Italy (Bologna,Firenze,Napoli, Roma e Torino)
(39) 199 11 99 22
All Countries (English)
(1) 440 646 3223
Morocco
(33) 825303132
All Countries (Español)
(1) 440 646 3650
Netherlands
(31) 10 266 55 80
Central America
Poland
(48) 22 32 60 707
Argentina
800.666.0320
Portugal
(1) 440 646 3223
Belize
(1) 440 646 3650
Slovakia
(420) 284015911
Bolivia
(54) 800 10 0632
Spain
(34) 902 30 93 30
Brazil
(55) 11 5189 9500
Sweden
(46) 46 19 93 91
Chile
800.53.0012
Switzerland (German)
(41) 0844 84 84 11
Colombia
01.800.700.2107
Switzerland (French)
(41) 0844 84 84 12
Costa Rica
0800.013.1215
Switzerland (Italian)
(41) 0844 84 84 13
Ecuador
58.212.949.0611
United Kingdom
(44) 01908 635245
El Salvador
(52) 55 5246 2010
North America
Guatemala
1.800.288.0108
Canada
(1) 440-646-3223
Honduras
(52) 55 5246 2010
United States
(1) 440-646-3223
Mexico
001.888.365.8677
Nicaragua
(52) 55 5246 2010
Panama
001.800.203.3475
Paraguay
(54) 11 5554 4000
Peru
0800.535.36
Suriname
(1) 440 646 3650
Uruguay
(54) 11 5554 4000
Venezuela
800.1.00.3062