PRODUCT NOTICE
Notice of Potential Product Concern
Rockwell Automation issues a Product Notice when it identifies a product(s) anomaly that may cause commercial or customer satisfaction concerns.
1756-OF8H HART Analog Output Module Shutdown
Reference: 2019-03-001
Date: March 2019
This Product Notice informs you of a potential anomaly that exists with the ControlLogix® HART Analog Output Module, catalog numbers 1756-OF8H, 1756-OF8H-CC, and 1756-OF8HK. In rare instances, modules manufactured October 1, 2016, through February 28, 2017, may shut down without fault state notification.
PRODUCT NOTICE
Page 2 of 5
– Product Identification –
The potentially affected product is the ControlLogix HART 8-channel Analog Output Module, catalog numbers 1756-
OF8H, 1756-OF8H-CC, and 1756-OF8HK. Potentially affected products were manufactured October 1, 2016, (date
code 2016/10/01) through February 28, 2017, (date code 2017/02/28).
On installed product, the product identification information may be found on the module nameplate label. The
Catalog number will be in the CAT field located above the CAT barcode. The manufactured date will be in the
DATE field located toward the bottom center of the nameplate and will be of the format YYYY/MM/DD, where
YYYY is the year, MM is the month code, and DD is the day of the month.
In the example shown to below, the catalog number is 1756-OF8H and the date of manufacture is 2016/09/23, or
September 23, 2016. The catalog number matches the product identification, but the manufacture date of this
example is not within the potentially affected product date range. This label as shown is an example only and
would not be subject to this notification.
For unopened product still within the product carton, the
product identification information may be found on the
shipping carton label. The catalog number will be in the
CAT field located on the left side of the label. The
manufactured date will be in the DATA field located on
the right side of the label and will be of the format
YYYY/MM/DD, where YYYY is the year, MM is the
month code, and DD is the day of the month.
Customers with unopened product are asked to return
product with the factory carton seal intact.
In the example shown to the left, the catalog number is
1756-OF8H and the date of manufacture is 2016/09/23,
or September 23, 2016. The catalog number matches
the product identification, but the manufacture date of
this example is not within the potentially affected
product date range. This label as shown is an example
only and would not be subject to this notification.
PRODUCT NOTICE
Page 3 of 5
– Description –
A potential anomaly exists with the ControlLogix® HART Analog Output Module, catalog number 1756-OF8H, and the conformal-coated variations 1756-OF8H-CC and 1756-OF8HK. In rare instances, modules manufactured October 1, 2016, through February 28, 2017, may shut down without fault state notification.
In a small percentage of modules manufactured within the listed date range, a component internal to the module may stop operating resulting in a loss of communication between processors within the module. The loss of communication causes the connection to the controller to time out. However, the module itself does not receive a fault state event and the module will continue to output last state instead of the configured fault state.
– Temporary Workarounds –
No workaround has been identified for this anomaly.
– Correction –
Correction requires replacing the module. 1756-OF8H modules that match the product identification information above may be returned for replacement or exchange. 1756-OF8H-CC and 1756-OF8HK conformal-coated variations may be returned for replacement only. Contact your Rockwell Automation Distributor, Sales Office, system provider, or other original place of purchase to discuss replacement options that may be available to you on this notification.
Reference this Product Notice PN 2019-03-001 when making your request. Customers with unopened product are asked to return product with the factory carton seal intact. Rockwell Automation will accept requests for replacement or exchange for a period of 18 months from the initial publication date of this Product Notice.
– Requested Customer Action –
Rockwell Automation requests you take the following actions:
Check if you have a product affected by this Product Notice. Refer to the Product Identification and Description sections of this document for product identification assistance.
If applicable, contact your local Rockwell Automation Distributor, Sales Office, system provider, or original place of purchase for replacement. Make sure to reference this Product Notice when requesting replacement product.
All returns should be over packed to prevent shipping damage during transit.
Continue to check incoming shipments for potentially affected product. Product in transit or in non-Rockwell Automation inventory may continue to contain potentially affected product for a period of time after the publication of this document.
If you need additional assistance, please contact Rockwell Automation Technical Support. See Appendix A for local telephone numbers. Customers without TechConnect℠ support contracts should reference this Product Notice when calling.
Customers with TechConnect support contracts may be able to chat online with support representatives. Reference this Product Notice when connected to a support engineer.
PRODUCT NOTICE
Page 4 of 5
The most current version of this Product Notice is posted on the Rockwell Automation Support Center http://www.rockwellautomation.com/knowledgebase, as ID number 1085150. Additional languages may also be available at the end of this article attached as downloadable PDF documents.
If this Product Notice does not affect you because you do not have the products any longer, or if you are a Distributor, Rockwell Automation asks that you forward a copy of this notice, with any identifying documentation, immediately to the person or company that now has the product. We also ask that you contact Rockwell Automation Technical Support and provide the location of the affected units.
We appreciate your immediate cooperation. If you have any questions, please contact us.
Sincerely,
ROCKWELL AUTOMATION
You can register for Automatic Product Safety Advisories and Product Notices from Rockwell Automation by email. Go to the Support web page at http://www.rockwellautomation.com/support and click the Search Knowledgebase – Get Answers link. Sign in with your TechConnect Account or free Rockwell Automation Member Account and you can subscribe to important product updates, including Product Safety Advisories and Product Notices.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
PRODUCT NOTICE
Page 5 of 5
Appendix A
Regional Technical Support Information
The following list can help you to contact the correct technical support center for your location. If your country is not listed, you can find a customer support number for your location by going to the Rockwell Automation Knowledgebase as https://rockwellautomation.custhelp.com. Mouse over Support and select Find Local Support, then enter your location information. If you have a TechConnect℠ support contract, please use the telephone number supplied to you with the contract.
Region / Country
Phone Number ( ) International Code
Region / Country
Phone Number ( ) International Code
Asia/Pacific
Europe
Australia
1 800 762 593
Austria
(49) 211 41553 664
China
400 620 6620
Belgium
(32) 2 716 8411
Hong Kong
+852 2887 4666
Czech Republic
(420) 28401 5911
India
1 800 2000 121
Denmark
(45) 43 466 006
Japan
03 3206 2785
Finland
(358) 958 447 419
Korea
(82) 2 2188 4400
France
(33) 825303132
Malaysia
1 800 80 4851
Germany
(49) 211 41553 664
New Zealand
0800 27 27 25
Hungary
(420) 28401 5911
Taiwan
080 902 0908
Ireland
(44) 01908 635245
Thailand
(66) 2936 1500
Italy (Brescia, Milano e Padova)
(39) 199 11 99 00
Caribbean
Italy (Bologna,Firenze,Napoli, Roma e Torino)
(39) 199 11 99 22
All Countries (English)
(1) 440 646 3223
Morocco
(33) 825303132
All Countries (Español)
(1) 440 646 3650
Netherlands
(31) 10 266 55 80
Central America
Poland
(48) 22 32 60 707
Argentina
800.666.0320
Portugal
(1) 440 646 3223
Belize
(1) 440 646 3650
Slovakia
(420) 284015911
Bolivia
(54) 800 10 0632
Spain
(34) 902 30 93 30
Brazil
(55) 11 5189 9500
Sweden
(46) 46 19 93 91
Chile
800.53.0012
Switzerland (German)
(41) 0844 84 84 11
Colombia
01.800.700.2107
Switzerland (French)
(41) 0844 84 84 12
Costa Rica
0800.013.1215
Switzerland (Italian)
(41) 0844 84 84 13
Ecuador
58.212.949.0611
United Kingdom
(44) 01908 635245
El Salvador
(52) 55 5246 2010
North America
Guatemala
1.800.288.0108
Canada
(1) 440-646-3223
Honduras
(52) 55 5246 2010
United States
(1) 440-646-3223
Mexico
001.888.365.8677
Nicaragua
(52) 55 5246 2010
Panama
001.800.203.3475
Paraguay
(54) 11 5554 4000
Peru
0800.535.36
Suriname
(1) 440 646 3650
Uruguay
(54) 11 5554 4000
Venezuela
800.1.00.3062
1201 South Second Street
Milwaukee, WI USA 53204
productsafety@ra.rockwell.com
PRODUCT NOTICE
Notice of Potential Product Concern
Rockwell Automation issues a Product Notice when it identifies a product(s) anomaly that may cause commercial or customer satisfaction concerns.
1756-OF8H HART Analog Output Module Shutdown
Reference: 2019-03-001
Date: March 2019
This Product Notice informs you of a potential anomaly that exists with the ControlLogix® HART Analog Output Module, catalog numbers 1756-OF8H, 1756-OF8H-CC, and 1756-OF8HK. In rare instances, modules manufactured October 1, 2016, through February 28, 2017, may shut down without fault state notification.
PRODUCT NOTICE
Page 2 of 5
– Product Identification –
The potentially affected product is the ControlLogix HART 8-channel Analog Output Module, catalog numbers 1756-
OF8H, 1756-OF8H-CC, and 1756-OF8HK. Potentially affected products were manufactured October 1, 2016, (date
code 2016/10/01) through February 28, 2017, (date code 2017/02/28).
On installed product, the product identification information may be found on the module nameplate label. The
Catalog number will be in the CAT field located above the CAT barcode. The manufactured date will be in the
DATE field located toward the bottom center of the nameplate and will be of the format YYYY/MM/DD, where
YYYY is the year, MM is the month code, and DD is the day of the month.
In the example shown to below, the catalog number is 1756-OF8H and the date of manufacture is 2016/09/23, or
September 23, 2016. The catalog number matches the product identification, but the manufacture date of this
example is not within the potentially affected product date range. This label as shown is an example only and
would not be subject to this notification.
For unopened product still within the product carton, the
product identification information may be found on the
shipping carton label. The catalog number will be in the
CAT field located on the left side of the label. The
manufactured date will be in the DATA field located on
the right side of the label and will be of the format
YYYY/MM/DD, where YYYY is the year, MM is the
month code, and DD is the day of the month.
Customers with unopened product are asked to return
product with the factory carton seal intact.
In the example shown to the left, the catalog number is
1756-OF8H and the date of manufacture is 2016/09/23,
or September 23, 2016. The catalog number matches
the product identification, but the manufacture date of
this example is not within the potentially affected
product date range. This label as shown is an example
only and would not be subject to this notification.
PRODUCT NOTICE
Page 3 of 5
– Description –
A potential anomaly exists with the ControlLogix® HART Analog Output Module, catalog number 1756-OF8H, and the conformal-coated variations 1756-OF8H-CC and 1756-OF8HK. In rare instances, modules manufactured October 1, 2016, through February 28, 2017, may shut down without fault state notification.
In a small percentage of modules manufactured within the listed date range, a component internal to the module may stop operating resulting in a loss of communication between processors within the module. The loss of communication causes the connection to the controller to time out. However, the module itself does not receive a fault state event and the module will continue to output last state instead of the configured fault state.
– Temporary Workarounds –
No workaround has been identified for this anomaly.
– Correction –
Correction requires replacing the module. 1756-OF8H modules that match the product identification information above may be returned for replacement or exchange. 1756-OF8H-CC and 1756-OF8HK conformal-coated variations may be returned for replacement only. Contact your Rockwell Automation Distributor, Sales Office, system provider, or other original place of purchase to discuss replacement options that may be available to you on this notification.
Reference this Product Notice PN 2019-03-001 when making your request. Customers with unopened product are asked to return product with the factory carton seal intact. Rockwell Automation will accept requests for replacement or exchange for a period of 18 months from the initial publication date of this Product Notice.
– Requested Customer Action –
Rockwell Automation requests you take the following actions:
Check if you have a product affected by this Product Notice. Refer to the Product Identification and Description sections of this document for product identification assistance.
If applicable, contact your local Rockwell Automation Distributor, Sales Office, system provider, or original place of purchase for replacement. Make sure to reference this Product Notice when requesting replacement product.
All returns should be over packed to prevent shipping damage during transit.
Continue to check incoming shipments for potentially affected product. Product in transit or in non-Rockwell Automation inventory may continue to contain potentially affected product for a period of time after the publication of this document.
If you need additional assistance, please contact Rockwell Automation Technical Support. See Appendix A for local telephone numbers. Customers without TechConnect℠ support contracts should reference this Product Notice when calling.
Customers with TechConnect support contracts may be able to chat online with support representatives. Reference this Product Notice when connected to a support engineer.
PRODUCT NOTICE
Page 4 of 5
The most current version of this Product Notice is posted on the Rockwell Automation Support Center http://www.rockwellautomation.com/knowledgebase, as ID number 1085150. Additional languages may also be available at the end of this article attached as downloadable PDF documents.
If this Product Notice does not affect you because you do not have the products any longer, or if you are a Distributor, Rockwell Automation asks that you forward a copy of this notice, with any identifying documentation, immediately to the person or company that now has the product. We also ask that you contact Rockwell Automation Technical Support and provide the location of the affected units.
We appreciate your immediate cooperation. If you have any questions, please contact us.
Sincerely,
ROCKWELL AUTOMATION
You can register for Automatic Product Safety Advisories and Product Notices from Rockwell Automation by email. Go to the Support web page at http://www.rockwellautomation.com/support and click the Search Knowledgebase – Get Answers link. Sign in with your TechConnect Account or free Rockwell Automation Member Account and you can subscribe to important product updates, including Product Safety Advisories and Product Notices.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
PRODUCT NOTICE
Page 5 of 5
Appendix A
Regional Technical Support Information
The following list can help you to contact the correct technical support center for your location. If your country is not listed, you can find a customer support number for your location by going to the Rockwell Automation Knowledgebase as https://rockwellautomation.custhelp.com. Mouse over Support and select Find Local Support, then enter your location information. If you have a TechConnect℠ support contract, please use the telephone number supplied to you with the contract.
Region / Country
Phone Number ( ) International Code
Region / Country
Phone Number ( ) International Code
Asia/Pacific
Europe
Australia
1 800 762 593
Austria
(49) 211 41553 664
China
400 620 6620
Belgium
(32) 2 716 8411
Hong Kong
+852 2887 4666
Czech Republic
(420) 28401 5911
India
1 800 2000 121
Denmark
(45) 43 466 006
Japan
03 3206 2785
Finland
(358) 958 447 419
Korea
(82) 2 2188 4400
France
(33) 825303132
Malaysia
1 800 80 4851
Germany
(49) 211 41553 664
New Zealand
0800 27 27 25
Hungary
(420) 28401 5911
Taiwan
080 902 0908
Ireland
(44) 01908 635245
Thailand
(66) 2936 1500
Italy (Brescia, Milano e Padova)
(39) 199 11 99 00
Caribbean
Italy (Bologna,Firenze,Napoli, Roma e Torino)
(39) 199 11 99 22
All Countries (English)
(1) 440 646 3223
Morocco
(33) 825303132
All Countries (Español)
(1) 440 646 3650
Netherlands
(31) 10 266 55 80
Central America
Poland
(48) 22 32 60 707
Argentina
800.666.0320
Portugal
(1) 440 646 3223
Belize
(1) 440 646 3650
Slovakia
(420) 284015911
Bolivia
(54) 800 10 0632
Spain
(34) 902 30 93 30
Brazil
(55) 11 5189 9500
Sweden
(46) 46 19 93 91
Chile
800.53.0012
Switzerland (German)
(41) 0844 84 84 11
Colombia
01.800.700.2107
Switzerland (French)
(41) 0844 84 84 12
Costa Rica
0800.013.1215
Switzerland (Italian)
(41) 0844 84 84 13
Ecuador
58.212.949.0611
United Kingdom
(44) 01908 635245
El Salvador
(52) 55 5246 2010
North America
Guatemala
1.800.288.0108
Canada
(1) 440-646-3223
Honduras
(52) 55 5246 2010
United States
(1) 440-646-3223
Mexico
001.888.365.8677
Nicaragua
(52) 55 5246 2010
Panama
001.800.203.3475
Paraguay
(54) 11 5554 4000
Peru
0800.535.36
Suriname
(1) 440 646 3650
Uruguay
(54) 11 5554 4000
Venezuela
800.1.00.3062